Humidity
measurement
HYGROCOR
RELATIVE HUMIDITY PROBE FOR OEM APPLICATIONS
Main characteristics
Measuring range: 0 ... 100 %rh, -20 ...+80 °C
Accuracy: ą 2 %rh, ą 0,2 °C
Output signal: 0 ... 1V (3 wire), Pt100 1/3 DIN
Supply voltage: 5...32VDC
Housing protection: IP65
Interchangeable sensor module S6000
Linearised and temperature compensated humidity measurement
Capacitive thin film humidity sensor
Sensor response time: 10 seconds
CE conformity
S6000
INTERCHANGEABLE SENSOR MODULE FOR
RELATIVE HUMIDITY
Main characteristics
Interchangeable without recalibration
Linearised and temperature compensated humidity measurement
Operating range: 0 ... 100 %rh, -30 ... +85 °C
Accuracy: ą 2 %rh, ą 0,2 °C
Output signal:
- Humidity: analogue and digital
- Temperature: Pt100 1/3 DIN
Capacitive thin film humidity sensor
Sensor response time: 10 seconds |
|